Reliable power connections start with the right technical decisions. In this article, NKS POWER answers three high-frequency questions about cable accessories — cold shrink termination cracking in winter, sheath circulating currents in long cables, and cable length allowance — with data and engineering essentials.
Silicone rubber cold shrink terminations are designed for an operating range of -65°C to +90°C, and the material itself stays flexible down to -65°C. But the real risk is not the operating temperature — it's the installation.
Parameter | Requirement | Notes |
Installation ambient temperature | ≥ 5°C | Below this, retraction force drops noticeably |
Low-temperature pre-conditioning | When ambient < 5°C, store accessories at ≥ 15°C for at least 4 hours | Restores full elastic recovery |
Core rod removal speed | 0.5–1 m/min | Pulling too fast causes stress concentration — the #1 cause of cracking |
For every 10°C drop in temperature, silicone retraction force decreases. Below 0°C, elastic recovery slows significantly. If the termination is installed without pre-heating, it may not shrink completely, causing uneven interfacial pressure, which leads to partial discharge — and eventually cracking or seal failure.
Winter installation checklist:
· Do not install below 0°C without pre-heating
· Never rush the core rod removal
· Never leave accessories outdoors unprotected overnight
NKS POWER cold shrink terminations are made from high-elasticity liquid silicone rubber and pass low-temperature recovery testing, validated for service down to -65°C. Cold weather should never compromise your power connection.
Grounding both sheath ends creates huge sheath circulating currents — up to 30%–80% of the conductor current — causing cable overheating, reduced current-carrying capacity, and accelerated insulation aging.
The Solution: Cross-Bonding (Section Transposition)
Divide the long cable into three equal sections, with an insulating joint between each section, then "transpose" the three-phase sheaths in a loop:
Phase A sheath end connects to Phase B's head
Phase B tail connects to Phase C's head
Phase C tail connects to Phase A's head
The three sections induce voltages of equal magnitude, 120° apart — they cancel each other out to nearly zero. The circulating current disappears, the sheath stops heating, and the cable's transmission capacity is restored.
· Applies to long cables typically over 2–4 km
· The three sections must be equal in length, tolerance within 5%
· Both ends are directly grounded
· Sheath voltage limiters are installed in the cross-bonding box
The calculated length seems sufficient — so why do engineers still order 5%–10% extra? The answer combines engineering standards and field experience (per GB 50217-2018).
Factor | Allowance |
Unusable remaining sections from whole cable drums (≤ 35kV, non-long-distance) | 5%–10% of calculated length |
Sag, wave curves and crossings in trays and ducts | 2.5% of total cable length |
Bending allowance for serpentine laying (≥ 35kV) | Required for thermal movement |
Fault repair — cutting out damaged sections and re-jointing | Reserve length |
Cables expand when energized and contract when de-energized — cycling through thermal expansion and contraction repeatedly. Serpentine (snake-shaped) laying absorbs this thermal movement, preventing mechanical stress from concentrating at joints and terminations. For 35kV and above, this bending allowance is a mandatory design consideration.
When a cable fault occurs, the damaged section must be cut out and re-jointed. If the remaining length isn't enough, the whole drum may need to be scrapped and replaced — a huge cost in materials, labour and downtime.
From -65°C cold shrink terminations to long-distance cable systems, NKS POWER offers a full range of MV & HV cable accessories — cold shrink terminations, joints, separable connectors, busbar connectors and surge arresters — manufactured to international standards and validated by independent KEMA type testing.